Voltage withstand test on GIS

With CPC 100 and CP RC you can perform a voltage withstand test in accordance with the IEC 62271-203 standards on GIS with an integrated “Power VT”. Our system can test GIS with a nominal voltage of up to 145 kV (with CP RC2) with a test voltage of up to 235 kV. The “Power VT” that is already integrated into the GIS replaces the test transformer, which would otherwise be necessary. This saves space and transport costs in your test procedures.

Our modular system can be transported and deployed without any extra equipment. Each component can be carried by just one person. Testing using the CPC 100 and CP RC also eliminates the need to vent, pump or refill SF6 gases.

CPC 100

Multi-functional test system for high-voltage assets

View Product

CP RC

Resonance circuit units for GIS testing

View Product