Safe Timing Measurements on Circuit Breakers Using Grounding on Both Sides
August 13, 2026
Thousands of customers around the world appreciate and value the numerous advantages of the CIBANO 500. It enables efficient execution of essential circuit breaker measurements, such as timing, static and dynamic contact resistance, travel, coil current and motor current, applicable to breakers of all voltage levels. Its extensive capabilities and efficient test methods for testing high voltage breakers are well recognized. Additionally, its built-in voltage/current source allows assessment of breaker performance under special conditions, such as overcurrent, undervoltage, or inadequate DC supply.
This article demonstrates the capabilities of CIBANO 500, highlighting an additional feature set beyond the traditional testing methods unavailable in other dedicated circuit breaker testing devices.
Specifically for budget-friendly medium voltage circuit breakers that include an undervoltage release, overcurrent release, or lack a trip coil entirely, it is crucial to have this feature to evaluate and record operational performance.
CIBANO 500’s undervoltage release test determines the specific control voltage level at which the undervoltage coil trips the breaker. The guided test procedure simplifies the examination of the undervoltage release significantly.
The test begins with the breaker entirely disconnected from the power supply. This means the main contacts are open because the undervoltage coil is not energized. As a first step, rated voltage is applied to the undervoltage coil, allowing the main contacts to close automatically via the closing coil using the CIBANO 500 or manually by the tester. Then, the supply voltage is gradually decreased until the release voltage threshold is reached, prompting the switch to open. At this point, the test is finished, and the release voltage is recorded.
In the CIBANO 500 overcurrent release test, its stable and controlled power supply is used to determine the current threshold that activates the specific overcurrent release input of the breaker, causing it to trip.
CIBANO 500s overcurrent release test provides a gradual increase in current pulse to the overcurrent release input until the circuit breaker's main contacts are opened. The trip current is recorded and can be used for reporting or failure analysis.
There are cases where our customers must also determine the switching time of circuit breakers lacking an electrical release mechanism. The CIBANO 500 addresses this issue by concurrently tracking the movement of the main contacts. As a result, the commencement of time measurement is adjusted from starting point as defined in the IEC standard, from the moment when the trip/close coil is energized, to the time when the movement begins.